Frysemaskin, vegghengt -18° -25°. Opptil 34,2 m³.

Varenr.
AN403-PED
Lager
Leveringstid normalt 1-2 uker
Pris
kr 52 530,00 Eks. MVA
Før
kr 61 800,00 Eks. MVA
Rabatt
kr 9 270,00 Eks. MVA
Frysemaskin, vegghengt -18° -25°. Opptil 29,2 m³. Frysemaskin for fryserom, vegghengt -18°C til -25°C. Opptil 34,2 m³. 230V/1-fas.
For lager, storhusholdning, butikk, restaurant, storkjøkken, etc.

DIAMOND – AN201-PED
Vegghengt frysemaskin - heng over-type.
Automatisk avisning, med gass kjølemedium.
Temperaturområde fra -18° til -25°C, (omgivelsestemperatur 32°C).
Kapasitet kjølerom: ved -20°C - 34,2 m³ / 34200 liter. 
Denne maskintypen er en "plugg-inn maskin", ferdig fylt med gass, klar til bruk.
Hengover-maskin er basert på at man skjærer ut to firkantspor i toppen på elementet, maskinen senkes så ned i de to små firkantsporene.
Silikoner eller skum rundt gjennomgangen. Monter dreneringsslangen. Maskinen er så klar til bruk.
Skal kjølemaskinen monteres i omgivelsetemperatur kaldere enn +10°C må det installeres vintertilpasset utstyr til kjøleenheten, be i tilfelle om tilleggspris på dette.
Kabel for dørvarmer og lys følger med.
Kjølemedium type R452a. 
Produsert i Europa.

(BxDxH) mm: 690x430(1184)x887
Temperatur: -15°C til -25°C
kW: 2,32
Volt: 400/3fas 50HZ (kan leveres i 230V/3-fas på forespørsel)
Bruttovekt: 162 kg
Fraktvolum: 1,17 m³

English:

Refrigerated group " Overlapping " T° -15°-25°
Cooling capacity 2343 (W/f) for chamber volume 29,2 m³ / 29200 Lit (T° internal -20° C & T° external +32° C).
Refrigerant expansion by thermostatic valve. Supplied with a cable for the connection of the door heater.
"Overlapping" refrigeration units. Unit certified in climatic class 5 (40°C Temperature - 40% Humidity).
All units are supplied as standard with a high pressure switch and KVL valve.
Automatic hot gas defrost with self-evaporation and overflow.
The evaporator drain pipe is equipped with a resistor to prevent ice formation.
Refrigerant gas R452a.
Supplied with cables and micro-switch for door and light (Porthole lights supplied as standard).
Microprocessor control with touch-sensitive keys. 

Attention: As standard, the ideal ambient operating temperature cannot be lower than 10°C.
Otherwise, provide: a compressor preheating (A-PR-R), a pressure switch for the condenser fan (A-PVC-R) as well as a heated electrical panel (A-TEC-R).
In this case, the operating temperature cannot be lower than -5°C. The unit must be protected from the weather when installed outdoors.

PLUS: All groups are supplied with a high pressure switch as standard.
The negative groups are equipped with a thermostatic valve.

(WxDxH) mm: 690x430(1184)x887
Temperature: -15°C to -25°C
kW: 2,32
Voltage 400/3N 50HZ (can be delivered in 230V/3N on demand)
Gross weight: 162 kg
Volume: 1,17 m³